In the old balloon and wagon boilers, the angle where the bottom joined
the sides scarcely ever remained sound for long when in contact with
the brickwork, and many of those that exploded have been found almost
corroded through where they stood upon the brickwork. The explosion
before alluded to and shown in Fig. 7, was caused by corrosion of the
bottom of the boiler where it was set on the brickwork. Many boilers
are so set that the brickwork of the flues is made to follow the shape
of the boiler, with as little space between as possible; but the slight
advantage gained in increased heating effect is far outweighed by the
impossibility of getting into the flues for examination. It is only
by having the flues sufficiently roomy that proper examination can be
made, and that the indications on the brickwork of leaking can be seen
and remedied, and corrosion arrested. A remarkable case of corrosion
occurred in a boiler with an oval shell, set upon a middle wall. The
flues were too narrow for a man to enter, and a leak in the bottom was
only discovered by the boiler nearly running empty while the engine
pumps were standing for a short time. It was subsequently found that
the whole bottom where it rested on the wall was extensively corroded
in a continuous line, and that explosion was only prevented by the
numerous stays across the bottom to compensate for the oval shape. Fig.
68, shows the position and extent of the corrosion, and the plate was
completely in holes at the parts indicated by the black marks. This
corrosion was supposed to have been going on for about three years.
[Illustration: _Fig. 69._]
[Illustration: _Fig. 70._]