Table 1 gives the sizes of fire-clay flue linings ordinarily provided
for boilers, furnaces, stoves, or convection heaters burning soft coal.
These sizes have proved satisfactory for average flat-grate furnaces
under normal conditions. Manufacturers of heating equipment
usually specify certain requirements in chimney construction and will
not guarantee the performance of their heaters unless these requirements
are met. Therefore their recommendations should be followed
when differing materially from the dimensions given in this bulletin.
Height of Chimney
A chimney should extend at least 3 feet above flat roofs and 2 feet
above the ridge of peak roofs. Where chimneys cannot be built
high enough above the ridge to prevent trouble from eddies caused by
wind being deflected from the roof, a hood may be provided with the
open ends parallel to the ridge. Eddies which force air down the
flues may be caused by building the chimney too near trees (fig. 5, _B_)
or a higher structure (fig. 6).
[1] Farmers' Bulletin 1698, Heating the Farm Home, contains information
on estimating the size of the heating plant needed for houses of
different sizes and for determining grate areas.
[Illustration: Figure 2.--Heavy masonry chimneys of this type are still
being built in rural areas. The thick walls, with unlined flues, are in
good condition after 75 years of continuous use.]
Table 1.--_Sizes of flue linings and heights of chimneys recommended for
flat-grate furnaces burning soft coal_[A]
Nominal size of flue lining
--------------------------------------------------- Height of
Grate Round (inside chimney top
area diameter) Rectangular (outside above grate
(Sq. at elevation dimensions) at elevation at elevation
ft.) indicated indicated indicated
- ---------------- -------------------------------------- --------------
SL 2K 4K 6K Sea Level 2,000 ft 4,000 ft 6,000 ft SL 2K 4K 6K
- ---------------- -------------------------------------- --------------
In In In In In In In In Ft Ft Ft Ft
1 8 8 8 10 8½ by 8½ 8½ by 8½ 8½ by 8½ 8½ by 13 22 26 32 36
2 10 10 10 10 8½ by 13 8½ by 13 8½ by 13 8½ by 13 24 29 35 41
3 10 10 12 12 8½ by 13 8½ by 13 13 by 13 13 by 13 26 33 41 49
4 12 12 12 12 13 by 13 13 by 13 13 by 13 13 by 13 30 37 45 49
5 12 12 15 15 13 by 13 13 by 13 13 by 18 18 by 18 32 37 43 52
6 15 18 18 18 18 by 18 18 by 18 20 by 20 20 by 20 30 37 47 56
7 18 18 18 18 20 by 20 20 by 20 20 by 20 20 by 20 32 41 49 64
8 18 18 18 18 20 by 20 20 by 20 20 by 20 20 by 20 35 42 56 10
[A] If anthracite is to be burned the area of the flue cross section may
be reduced about 25 percent.